描述
产品简要说明
RMV-112D是DEIF专为电力系统电压异常防护设计的高精度继电器,核心能力包括:
双阈值保护:欠压(80%~100%)与过压(100%~120%)独立可调
智能触点配置:支持常开/常闭触点自定义,适配陆地/船舶场景
快速响应:故障检测时间≤20ms
产品详细说明
1.保护逻辑与功能
电压监测机制
三相测量:
同时监测Ua、Ub、Uc,支持不平衡电压补偿
阈值设定:
欠压触发点80%~100%额定电压,过压触发点100%~120%(步长0.1%)
动作特性
模式触发条件输出触点类型
欠压保护任意相电压<U<设定值常闭触点延时断开
过压保护任意相电压>U>设定值常开触点瞬时闭合
2.系统集成能力
自锁电路:
故障触发后触点可锁定(需手动复位或断电复位)
协同设备:
可与RMF-112D(频率保护继电器)组成完整电网保护链
产品概述:RMV-112D
作为DEIF电力保护产品线的基础型号,RMV-112D通过灵活的触点配置与高精度监测算法,为发电机、变压器等设备提供可靠的电压异常防护,尤其适用于船舶电网的特殊安全需求。
Product brief description
RMV-112D is a high-precision relay designed by DEIF for power system voltage abnormality protection,with core capabilities including:
Double threshold protection:undervoltage(80%-100%)and overvoltage(100%-120%)are independently adjustable
Intelligent contact configuration:Supports customization of normally open/normal closed contacts,adapted to land/ship scenarios
Quick response:fault detection time≤20ms
Product details
1.Protection logic and functions
Voltage monitoring mechanism
Three-phase measurement:
At the same time,Ua,Ub,Uc are monitored,and unbalanced voltage compensation is supported
Threshold setting:
Undervoltage trigger point 80%to 100%rated voltage,overvoltage trigger point 100%to 120%(step length 0.1%)
Action Characteristics
Mode Trigger Condition Output Contact Type
Undervoltage protection Any phase voltage<U<set value Normally closed contact delay disconnection
Overvoltage protection Any phase voltage>U>Set value Normally open contact instantaneously closed
2.System integration capability
Self-locking circuit:
The contact can be locked after the fault is triggered(reset manually or reset off)
Collaborative equipment:
Can form a complete grid protection chain with RMF-112D(frequency protection relay)
Product Overview:RMV-112D
As the basic model of the DEIF power protection product line,RMV-112D provides reliable voltage abnormality protection for generators,transformers and other equipment through flexible contact configuration and high-precision monitoring algorithms,which is especially suitable for the special safety needs of marine power grids.