描述
Schneider 140CPS12400R是施耐德电气(Schneider Electric)Modicon Quantum系列中的一款冗余电源模块,专为工业自动化系统设计,提供高可靠性与灵活的供电方案。以下是其核心功能与技术特点的综合解析:
一、核心功能与技术特点
冗余供电设计
采用双电源冗余模式,确保系统在单个电源故障时仍能稳定运行,适用于对连续性要求极高的工业场景(如电力、化工、轨道交通)。
宽电压输入与输出
输入电压:支持115V/230V AC(50/60Hz),输入电压范围宽(93-276V AC),适应不同电网环境。
输出电压:提供5V DC总线电压,支持Modicon Quantum系列CPU、接口模块及I/O模块供电。
多种供电模式
独立模式:适用于3A或8A低负载配置,无需冗余。
独立可叠加模式:通过并联多个模块扩展供电能力,适合高负载需求。
独立冗余模式:双模块热备份,实现不间断供电。
保护与安全特性
过流/过压保护:内置过流、过压及短路保护电路,防止设备损坏。
浪涌抑制:输入浪涌电流最大值为38A(115V)或19A(230V),提高抗干扰能力。
二、技术参数
额定输出电流:独立模式下最大5.1A,冗余模式下最大8A(60℃时)。
功率因数:0.5,效率优化以适应工业环境需求。
防护等级:未明确标注,但符合工业级防护标准(如IP20)。
工作温度:-20°C至60°C(存储温度-40°C至70°C)。
Schneider 140CPS12400R is a redundant power supply module in Schneider Electric’s Modicon Quantum series,designed for industrial automation systems,providing high reliability and flexible power supply solutions.The following is a comprehensive analysis of its core functions and technical features:
I.Core functions and technical features
Redundant power supply design
The dual power supply redundancy mode is adopted to ensure that the system can still operate stably when a single power supply fails.It is suitable for industrial scenarios with extremely high continuity requirements(such as electricity,chemical industry,and rail transportation).
Wide voltage input and output
Input voltage:supports 115V/230V AC(50/60Hz),with a wide input voltage range(93-276V AC),which can adapt to different power grid environments.
Output voltage:Provides 5V DC bus voltage to support Modicon Quantum series CPU,interface module and I/O module power supply.
Multiple power supply modes
Independent mode:Suitable for 3A or 8A low-load configuration,without redundancy.
Independent superimposable mode:Expand the power supply capacity by connecting multiple modules in parallel,suitable for high load requirements.
Independent redundant mode:dual module hot backup to achieve uninterrupted power supply.
Protection and safety features
Overcurrent/overvoltage protection:built-in overcurrent,overvoltage and short-circuit protection circuits to prevent equipment damage.
Surge suppression:the maximum input surge current is 38A(115V)or 19A(230V),which improves anti-interference ability.
2.Technical parameters
Rated output current:maximum 5.1A in independent mode,maximum 8A in redundant mode(at 60°C).
Power factor:0.5,efficiency optimized to meet the needs of industrial environments.
Protection level:not clearly marked,but meets industrial protection standards(such as IP20).